Application Scenarios
● Hazardous areas with explosive gas mixtures: Zone 1, Zone 2.
● Explosive gas mixtures: IIA, IIB, IIC.
● Hazardous areas with explosive dust: Zone 20, Zone 21, Zone 22.
Product Features
1. Utilizes high-quality key components from internationally renowned manufacturers, featuring a meticulously designed structure and optimally matched systems.
2. The unit is reliable, durable, stable in operation, energy-efficient, with a wide capacity regulation range. It is compact, small in size, low in noise and vibration, and easy to operate and maintain.
3. Incorporates the most advanced explosion-proof technology to ensure superior explosion-proof performance and safe, reliable operation.
4. Widely used in hazardous locations with combustible gases, such as the military, petroleum, chemical, and pharmaceutical industries.
Technical Parameters
Item | BKT-1000 | BKT-1200 | BKT-1600 |
Capacity Control | 10~100% | 10~100% | 10~100% |
Cooling Capacity | 1000Kw | 1200Kw | 1600Kw |
Noise Level (IPLV Condition) | 5.96 | 6.02 | 6.21 |
Compressor Type | Single-stage | Single-stage | Single-stage |
Power Supply | 380V 3N~ 50Hz | 380V 3N~ 50Hz | 380V 3N~ 50Hz |
Compressor |
Rated Power | 191Kw | 227Kw | 293Kw |
Compressor Connected Power | 220Kw | 260Kw | 300Kw |
Refrigerant |
Charge Volume | 50L | 50L | 50L |
Refrigerant Type | R134a | R134a | R134a |
Evaporator |
Water Flow | 172m³/h | 206m³/h | 275m³/h |
Water Pressure Drop | 75Kpa | 75Kpa | 75Kpa |
Evaporator Number of Passes | 2 | 2 | 2 |
Connection Size | 200mm | 200mm | 200mm |
Condenser |
Water Flow | 215m³/h | 255m³/h | 344m³/h |
Water Pressure Drop | 70Kpa | 70Kpa | 70Kpa |
Condenser Number of Passes | 2 | 2 | 2 |
Connection Size | 200mm | 200mm | 200mm |
Connection Method | Flanged connection | Flanged connection | Flanged connection |
Dimensions & weight |
Width | 3630mm | 3630mm | 3630mm |
Depth | 1680mm | 1680mm | 1680mm |
Height | 2060mm | 2060mm | 2060mm |
Net Weight | 5800Kg | 6100Kg | 6700Kg |
Operating Weight | 6390Kg | 6800Kg | 7360Kg |
Explosion-proof Marking |
Explosion-proof Marking | Ex d ib mb IIB / IIC T4 Gb | Ex d ib mb IIB / IIC T4 Gb | Ex d ib mb IIB / IIC T4 Gb |